ymzdcs

Siemens FDL241-9-CN Linear Beam Smoke Detector

1. Overview of Siemens FDL241-9-CN

People also know the Siemens FDL241-9-CN Linear Beam Smoke Detector as the Siemens FDL241-9. Engineers designed this linear smoke detector for reliable smoke detection. It works well in large areas like warehouses, atriums, industrial sites, and commercial buildings.

The Siemens FDL241-9-CN detector meets the national standard GB14003-2005 for smoke fire detectors. It uses light attenuation by smoke to detect early-stage fires accurately.

The system consists of a transmitter and receiver housed in a single unit. The transmitter sends out an infrared (IR) light beam to a prismatic reflector. The reflector then sends the beam back to the receiver. The receiver converts the returning IR signal into an electrical signal that a microprocessor analyzes.

When smoke particles enter the detection path, the infrared beams intensity weakens. When the attenuation level exceeds a certain limit, the FDL241-9 triggers an alarm.

The system sends this alarm to the fire alarm controller. This shows that there is smoke or fire. The detector has a built-in alarm light for local status. It also uses ASAtechnology(Advanced Signal Analysis) to reduce false alarms.

The Siemens FDL241-9-CN Linear Beam Smoke Detector provides reliable smoke detection over long distances of 5 to 100 meters. This makes it perfect for protecting high ceilings or open areas from fire.

2 .Key Parameters of Siemens linear smoke detector fdl241-9linear smoke detector

Complies with GB14003-2005 national standard for linear beam smoke detectors

Transmitter and receiver design utilizing infrared light emission and reflection

Detects fires according to the principle of light attenuation by smoke

Signal weakening triggers an alarm once the predefined threshold is reached

The distance measurement feature helps identify and compensate for environmental factors

Built-in alarm indicator light for visual alarm confirmation

Reliable smoke detection in large rooms (indoor applications)

Detection range: 5100 meters

ASAtechnologyfor advanced signal analysis and reduced false alarms

Three selectable sensitivity levels for flexible configuration

Event control detection method

Transmits four hazard levels to the control unit

Microprocessor-based signal analysis for accuracy and reliability

Self-testing and automatic contamination compensation functions

Resistant to external light and electromagnetic interference

Single-unit design housing both transmitter and receiver

D-BUS communication protocol with independent addressing

Multiple reflectors available for various distance configurations

Indicator LED: Flashes every second (normal operation) / Constant on (alarm state)

Operating voltage: 1233 VDC

Static operating current: 0.8 mA

External and programmable door light output

Operating temperature: 25°C to +60°C

Storage temperature: 30°C to +75°C

Humidity: 95% RH

Terminal wire size: 0.21.5 mm²

Protection rating: IP65 (EN60529/IEC529)

Weight: 0.440 kg

Colour: Pure white (RAL9010)

Dimensions (with FDLB291): 135 × 135 × 115 mm

3. Key Features of siemens fdl241 9 Detector

ASA Linear Smoke Detector Unit: Incorporates Advanced Signal Analyzing Technology for stable performance and reduced false alarms.

Infrared Detection Principle: Uses infrared light attenuation to detect smoke presence effectively.

Reliable Smoke Detection in Large Spaces: Designed for high-ceiling environments, such as airports, atriums, tunnels, and industrial plants.

Microprocessor Control: Ensures precise signal interpretation and alarm triggering.

Automatic Compensation: Maintains consistent sensitivity even as optical surfaces accumulate dust or dirt.

Visual Status Indication: Integrated LED indicators show both normal operation and alarm conditions.

Flexible Installation: Adjustable for detection ranges from 5 to 100 meters, compatible with multiple reflector options.